Aagard ZSE40 Setup
3711 Iowa Street Phone 320.763.6043Alexandria, MN 56308 www.aagard.comPage 1 of 4 ZSE40 Vacuum Switch -ISE40A Pressure Switch - PF2A Flow Switch Setup.docZSE40 Vacuum Switch Setup1. Press and hold the SET key until the display shows a unit of measurement such as kPa,psi, ect.2. Then using the UP and Down keys navigate to the correct unit which is InHg for inchesof mercury.3. Now return to the main display by pressing the SET key. This should bring you to ascreen with a low number on it for the current/live reading.4. Press the SET key again and the display should read P_1 toggling to a number and thenback again.5. Using the Arrow Keys adjust the number to P_1 setting on prints which would be theON trigger point of the vacuum switch.6. Press the SET key again to go to P_2 and set to P_2 settings on prints which would bethe OFF trigger point of the vacuum switch. And press the SET key again.7. Displayed will be P_3 which we leave set at its default. Press the SET key again so thedisplay reads P_4 and again leave this set at its default.8. Now press the SET key until you are back to the main page which should have a lownumber reading on it such as 0.0 to 0.4.9. The Out 1 indicator should not be illuminated at this point and you are ready forproduction.System vacuum switch settings – P_1 = 18; P_2 = 15Secondary vacuum switch settings – P_1 = 15; P_2 = 12By setting these switches up in this manner the Vacuum switch will provide an output when we getto 17.0 InHg and it will not loose its signal unless we drop below 15.0 InHg. |