PROGRAMMING INSTRUCTIONSPlease read all 3 steps before programming1. Enter a programming function by pressing button the numberof times as the desired function number from the tables below(e.g., press twice for function 2, time delay).2. LED will flash back the selected function’s current setting(e.g., 5 flashes for 10 minute time delay). To change setting,proceed to step 3 before flash back sequence repeats 3 times.To exit the current function or to change to a different function,wait for sequence to repeat 3 times then return to step 1.3. Press button the number of times indicated in the particularfunction’s detailed table for the NEW desired setting (e.g.,press 3 times for 5 min). As confirmation of setting change,LED flashes back the NEW setting 3 times before exiting.DETAILED FUNCTION TABLES2 = Time Delay1 30 sec 4 7.5 min 7 15.0 min2 2.5 min 5 10.0 min* 8 17.5 min3 5.0 min 6 12.5 min 9 20.0 min3 = Idle Time Until Dim1 30 sec 4 7.5 min* 7 15.0 min 10 Disable2 2.5 min 5 10.0 min 8 17.5 min3 5.0 min 6 12.5 min 9 20.0 min4 = 100 Hour Burn-In / Auto Set-Point1 Disabled*2 Enabled3 Enabled then run Auto-Setpoint4 Run Auto Set-Point5 Blink back Set-Point22 The LED will blink back the ten’s digit, then pause, then blink backthe one’s digit. For a “0” the LED will blink very rapidly. The sequenceis repeated 3 times.5 = Ten’s Digit of Set-Point1 10 fc 4 40 fc 7 200 fc2 20 fc 5 50 fc 8 Disabled*3 30 fc 6 100 fc 10 0 fc**6 = One’s Digit of Set-Point1 1 fc 4 4 fc 7 7 fc 10 0 fc2 2 fc 5 5 fc* 8 8 fc3 3 fc 6 6 fc 9 9 fc7 = Sunlight Discount Factor1 x/1*** 4 x/4* 7 x/7 10 x/102 x/2 5 x/5 8 x/83 x/3 6 x/6 9 x/98 = Incremental Set-Point Adjustment1 Decrease 1 fc 2 Increase 1 fc11 = Photocell Mode1 Full On/Off Control* 2 Inhibit Only Control12 = Dual Technology (MicrophonicsTM)1 On* 2 Off15 = Photocell Dim Range (High)1 Min 4 30% 7 60% 10 90%2 10% 5 40% 8 70% 11 100%*3 20% 6 50% 9 80%16 = Photocell Dim Range (Low)1 Min 4 30% 7 60% 10 90%2 10%* 5 40% 8 70% 11 100%3 20% 6 50% 9 80%21 = Photocell Transition Off Time1 45 sec 3 5 min* 5 15 min 7 25 min2 2 min 4 10 min 6 20 min22 = Photocell Transition On Time1 45 sec* 3 5 min 5 15 min 7 25 min2 2 min 4 10 min 6 20 min23 = Occupied Bright Level1 10% 4 40% 7 70% 10 100%*2 20% 5 50% 8 80%3 30% 6 60% 9 90%24 = Unoccupied Dim Level1 10%* 4 40% 7 70% 10 100%2 20% 5 50% 8 80%3 30% 6 60% 9 90%* DEFAULT SETTING2 Time Delay • • • •3 Idle Time Until Dim •4 100 Hr Burn-In /Auto Set-Point • • • •5 Ten’s Digit of Set-Point • • • •6 One’s Digit of Set-Point • • • •7 Sunlight Discount Factor • • • •8 Incremental Set-PointAdjustment • • • •11 Photocell Mode • • • •12 Dual Tech. (MicrophonicsTM)1 •15 Photocell Dim Range (High) • •16 Photocell Dim Range (Low) • •21 Photocell Transition Off Time • • • •22 Photocell Transition On Time • • • •23 Occupied Bright Level •24 Unoccupied Dim Level •FUNCTIONS Standard P ADC ADCX1 PDT SENSORS ONLYOptions* DEFAULT SETTING ** P, ADC, and ADCX DEFAULT*** nCM(R)(B)-6 or nCM(R)B-50 UNITS’ DEFAULT