LL30 SERIESINSTALLATION INSTRUCTIONSSAVE THESE INSTRUCTIONS!READ CAREFULLY AND FOLLOW ALL INSTRUCTIONS FOR YOUR OWN SAFETY• DISCONNECT AC POWER SUPPLY BEFORE SERVICING.• Installation and servicing of this equipment should be performed by qualified service personnel only.• Ensure the electricity connections conform to the National Electrical Code and local regulations if applicable.• Do not mount near gas or electrical heaters.• Equipment should be mounted in locations and at heights where it will not readily be subjected to tampering byunauthorized personnel.• The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition.Any modification or use of non-original components will void the warranty and product liability.• Do not use this equipment for other than intended use.800.533.3948 • www.barronltg.com10070057 Rev 4 - 02/14INSTALLATION INSTRUCTIONS1. Mount steel bracket (5) to junction box, using hardware provide with junction box.2. All Electrical connection should be made inside junction box.Make Electrical Connection as follows:120V AC 277V ACWhite - Common White - CommonBlack - 120V Orange - 277VGreen - Ground Green - GroundNote: Cap unused leads to prevent shorting.3. Mount Emergency light unit to the steel bracket (5).4. Remove lamp cover (1) by removing the cover hold plug (6).5. Remove cover housing (2) by loosening four cover housing screws (7).6. For additional mounting support knockout key hole and use appropriate hardware for mounting surface.7. Use supplied wire nuts to connect lamp leads with lamp power leads (Purple and Yellow).8. Make appropriate battery lead connection:• Red lead to positive (+) terminal.• Blue lead to negative (-) terminal.9. Reinstall cover housing (2) carefully to avoid damaging LED AC ON indicator, retightening for screws (7)10. Reinstall lamp cover (1) by replacing the cover hold plug (6).11. Turn on power supply.1