1808-25502/00INSTALLATION INSTRUCTIONST-55 SPACE TEMPERATURE SENSOR WITH OVERRIDET-56 SPACE TEMPERATURE SENSOR WITH OVERRIDE & SETPOINT ADJUSTMENTCOMPONENT LISTThe Model T-55 Space Temperature Sensor with Override and T-56 Space Temperature Sensorwith Override & Setpoint Adjustment consists of the following components:• (1) Space temperature sensor• (2) 6-32" x 1" round head machine screwsLOCATING THE SENSORThe T-55 and T-56 space temperature sensors measure building interior temperature and should belocated on an interior building wall. The sensor wall plate accommodates the NEMA standard 2 x 4junction box. The sensor can be mounted directly on the wall surface if acceptable by local codes.Do not mount the sensor in drafty locations such as near air conditioning or heating ducts, over heatsources such as baseboard heaters, radiators, or directly above wall mounted lighting dimmers. Donot mount the sensor near a window that may be opened, or near a wall corner or door. Sensorsmounted in these areas will have inaccurate and erratic sensor readings.Mount the sensor approximately 5 ft from the floor, in an area representing the average temperaturein the space. Allow at least 4 ft between the sensor and any corner and mount the sensor at least 2 ftfrom an open doorway.Note: Clean sensor with damp cloth only. Do not use solvents.TO INSTALL THE T-55 AND T-56 SENSOR(See Figure 1 below)1. Locate the two Allen-type screws at the bottom of the sensor.2. Turn the two screws clockwise to release the cover from the sensor wall mounting plate.3. Lift the cover from the bottom and then release it from the top fasteners.4. Feed the wires from the electrical box through the opening in the center of the sensor mount-ing plate.