INSTRUCTIONS1. Ensure correct sensor model was chosen for Input Volt-age of application.2. Mount the sensor to a DIN rail using integrated mountingclip on backside of transducer.3. Connect input voltage -(5) & +(6) and output wiringusing up to 22-12 AWG copper conductors only insu-lated to 75°C minmum and tighten to 6-in lbs. Referto “Output Wiring” section for voltage and impedancerecommendations.4. Connect 24 VAC or DC power supply fused to 5 A toterminals 3-4.Do not connect power supply and signal circuits together.There is no isolation.VTD SERIESDC Voltage TransducersRanges 15, 25, 50, 150, 300 and 600 Volts4-20 mA, 0-5/10 VDC OutputsVTD 1 - 420 - 24U - DINOUTPUT:420 - 4-20 mA005 - 0-5 VDC010 - 0-10 VDCVOLTAGE INPUT RANGE:0 - 15 VDC1 - 25 VDC2 - 50 VDC3 - 150 VDC4 - 300 VDC5 - 600 VDCSENSOR TYPE:VTD - DC Voltage TransducersModel Number KeySpecificationsQuick “How To” GuideCASE STYLE:DIN - DIN rail compatiblePOWER SUPPLY:24U - Nominal 24 VAC/VDC3511 Charter Park Drive, San Jose, CA 95136Phone: 800-959-4014 or 408-871-7510Fax: 408-871-7515sales@nktechnologies.com, www.nktechnologies.com 292182001 Rev 9Know Your PowerOther NK Technologies Products Include:AC & DC Current TransducersAC & DC Current Operated Switches1 & 3Power TransducersCurrent & Potential Transformers (CTs & PTs)Power Supply 24 VAC/VDC External PowerA fuse rated maximum 5 A shall beplaced in series with the main input,24 VDC, power terminal.(20-45 VDC, 22-38 VAC), <2 VAPower and output are not isolated. Do not connect together.Input Range: Input 15 V: 25 KΩ, 25 V: 42 KΩ,Impedance 50 V: 82 KΩ, 150 V: 250 KΩ,300 V: 500 KΩ, 600 VDC: 1.00 MΩOutput Signal 4-20 mA (capped at 24 mA max)0-5 VDC (capped at 5.75 VDC)0-10 VDC (capped at 11.5 VDC)Response Time 250 ms (to 90% of step change)Accuracy < 1% Full ScaleLinearity < 0.5%Output Loading 4-20 mA: < 500 ohm0-5/10 V: > 10 K ohmIsolation Voltage 2200 VACFrequency Range DCEnclosure UL94 V-0 RatedEnvironmental Operating Temp.-4 to 140°F (-20 to 60°C)0–95% RH, Non-condensingPollution Degree 2Altitude to 6561 ft (2000 meters)Listings UL/cUL listed, CEWarning! Risk of dangerSafe operation can only be guaranteed if thetransducer is used for the purpose for which itwas designed and within the limits of the techni-cal specifications. When this symbol is used,it means you must consult all documentation tounderstand the nature of potential hazards andthe action required to avoid them.Warning! Risk of electrical shockWhen operating the transducer certain parts maycarry hazardous live voltage (e.g. primary con-ductors, power supply). The transducer shouldnot be put into operation if the installation is notcomplete.For products intended for the EU market, the following is ap-plicable to the CE compliance of the product:The VTD series comply with EN 61010-1 CAT III 600 V maxmeasurement category. Power source overvoltage category I asdefined per EN 61010-1