Instruction SheetPart 331276B02 2010 Nordson CorporationP/N 331276B02Series EPC-30 Current-to-Pressure (I/P)TransducerWARNING! Allow only personnel with appropriate training and experienceto operate or service the equipment. The use of untrained or inexperiencedpersonnel to operate or service the equipment can result in injury, includingdeath, to themselves and others, and damage to the equipment.IntroductionThis instruction sheet contains the procedure for installing thecurrent-to-pressure (I/P) transducer (kit P/N 772033).If the Eclipse EPC-30 pattern control is equipped with an optionalinput/output (I/O) board, the I/P transducer can be installed to providerun-up control for the system. Refer to the Eclipse EPC-30 pattern controlmanual for setting the run-up control.SpecificationsThe following table lists specifications for the I/P transducer.Item Specification NoteAir supply input pressure 8.6 − 10.3 bar (125 − 150 psi) AAir supply output pressure 0.2 − 8.3 bar (1 − 120 psi) AInput impedance 260 ohms (nominal)Input signal 4 − 20 mA VDC BNOTE A: The transducer was calibrated using a 6.6−6.9 bar (95−100 psi) air supply.B: With a 6.6−6.9 bar (95−100 psi) air supply, the output should be 0−0.3 bar (0−5 psi) with a 4 mA signal or6.0−6.4 bar (87−93 psi) with a 20 mA signal.