Project Name / Date Division 23 52 33.13 - 1DIVISION 23 52 33.13FINNED WATER-TUBE BOILERSPART 1 - GENERAL1.1 SUMMARYA. Section includes gas-fired, copper finned-tube hydronic heating boilersB. Related SectionsSpecifier Note: Use as needed1. Building Services Piping – Division 23 21 002. Breeching, Chimneys, and Stacks (Venting) – Division 23 51 003. HVAC Instrumentation and Controls – Division 23 09 004. Electrical – Division 23 09 331.2 REFERENCESA. ANSI Z21.13/CSA 4.9B. ASME, BPV Section IVC. 2006 UMC, Section 1107.6D. ANSI/ASHRAE 15-1994, Section 8.13.6E. National Fuel Gas Code, ANSI Z223.1/NFPA 54F. I=B=RG. National Electrical Code. ANSI/NFPA 70H. ASME CSD-1, 2009 (when required)1.3 SUBMITTALSA. Product data sheet (including dimensions, rated capacities, shipping weights, accessories)B. Wiring diagramC. Warranty informationD. Installation and operating instructions1.4 QUALITY ASSURANCEA. Regulatory Requirements1. ANSI Z21.13/CSA 4.92. Local and national air quality regulations for low NOx (< 20 PPM NOx emissions) boilersB. Certifications1. CSA2. ASME H Stamp and National Board Listed3. ISO 90011.5 WARRANTYA. Limited one-year warranty from date of installationB. Limited twenty-year thermal shock warrantyC. Limited ten-year closed-system heat exchanger warrantyPART 2 - PRODUCTS2.1 MANUFACTURERA. Raypak, Inc.1. Contact: 2151 Eastman Ave., Oxnard, CA 93030; Telephone: (805) 278-5300;Catalog No.: 2000.952DEffective: 9-1-09Replaces: 5-1-08HI DELTA® , TYPE H - MODELS 992BE-2342BESUGGESTED SPECIFICATIONS