INSTRUCTIONi Read this instruction before installationand wiring of the productMTISConsult documentation in all cases where this symbolis used, in order to find out the nature of the potentialhazards and any actions to be taken1MTISMechanical capillary thermostatThe MTIS electro-mechanical thermostats are constructed arounda fluid-filled bulb and sensor housing that transfers the changes intemperature to a change-over relay. The relay is capable of breakingup to 15 A at 230 V AC. Each model also has a sensor element and amounting clamp for direct fixing on a pipe.Technical dataSensor element Liquid-filled copper bulb for contactContacts Dust-tight microswitches with SPDTcontacts (heat/cool)Switch capacity 15 (8) A, 24...250 V ACAmbient temperature -35…+65°CAmbient humidity 10…90 % RH (non-condensing)Housing Bayblend® base, ABS coverProtection class IP65Isolation class 1Weight 410 gStorage temperature -40…+70°CStorage humidity up to 95% RHArticle Tempera-ture rangeHysteresis Max. bulbtemp.HiddensetpointMTIS60S 0...60°C 2…20 K 75°CMTIS60SH 0...60°C 2…20 K 75°C *MTIS90S 20...90°C 2…20 K 95°CMTIS90SH 20...90°C 2…20 K 95°C *Before installation or maintenance, the power supply must first be discon-nected in order to prevent potentially lethal electric shocks! Installation ormaintenance of this unit should only be carried out by skilled professio-nals.InstallationThe unit can be mounted in any position.Remove the external knob and unscrew both screws on the cover. Usethe supplied screws when mounting on wall or other surface.WiringHeating:Connect to the red and blue terminal. The contact will open when thetemperature rises.Cooling:Connect to the red and white terminal. The contact will open when thetemperature drops.Logic activationResetThe set range may be reset by carefully turning the screw under thecover.+-Low Voltage Directive (LVD) standardsThis product conforms to the requirements of the European LowVoltage Directive (LVD) 2014/35/EU through product standardsEN 60335-1.RoHSThis product conforms to the Directive 2011/65/EU of the EuropeanParliament and of the Council through standard EN 50581:2012.ContactAB Regin, Box 116, 428 22 Kållered, SwedenTel: +46 31 720 02 00, Fax: +46 31 720 02 50www.regincontrols.com, info@regincontrols.com12973BJUN 17ENRedBlueWhiteONONOFFOFFΔNSΔNSHeatingContacts red-blueCoolingContacts red-whiteΔNS: HysteresisTSET: Setting setpointON: Closed contactOFF: Open contact