Automation Components, Inc.2305 Pleasant View Road | Middleton, WI 53562Phone: 1-888-967-5224 | Website: workaci.comPage 1Version: 15.0I0000777Version: 15.0I0000777FIGURE 1: DLP DIMENSIONSDLP SERIESInstallation & Operation Instructions Phone: 1-888-967-5224Website: workaci.com4.35"(110.43 mm) 2.23"(56.52 mm)2.48"(62.99 mm)5.56"(141.29 mm)6.02"(152.82 mm)CORDGRIP /1/2 “ CONDUIT FITTINGHIGH PRESSURE PORTLOW PRESSURE PORT-H-LPRECAUTIONS• Do not switch pressure range and outputmode when power is on. Make sure to power offthe unit first, then set the DIP Switches to thecorrect positions and then power on thetransmitter.GENERAL INFORMATIONThe DLP Series is based on a piezoresistive, siliconsensing element which senses Differential Pressureand provides an analog output. Field selectableanalog outputs include 0-5 and 0-10 VDC, or 4-20mA which correlate to a uni or bi-directionalpressure range from 0-0.1” up to 0-40” of watercolumn, depending on your model selection. Eachunit has up to 8 field selectable, uni or bi-directionalranges (see Figure 6 p. 3).MEDIAThe DLP can be used to monitor the differentialpressure in any application that uses dry air or inertgas.MountingFind a suitable location for the enclosure. The DLPhas 2 two mounting holes located on the top andbottom flanges. Drill pilot holes for the (2) #8 x 3/4”self-drilling screws(supplied). Use the enclosure flange as a guide, or use the dimensions listed in Figure 1.Mount the unit vertically with the brass fittings pointing towards the ground. This ensures that anycondensation that may form in the tubing does not have an effect on the pressure sensor. If mounting theunit horizontally, a slight zero shift may occur and care must be taken to prevent moisture from buildingup in the sensor.FIGURE 2: DIN RAIL MOUNTINGDIN RAILDIN RAILDIN RAILCLIP