Automation Components, Inc.2305 Pleasant View Road | Middleton, WI 53562Phone: 1-888-967-5224 | Website: workaci.comPage 1Version: 6.0I0000691RD2432D SERIESInstallation & Operation Instructions Phone: 1-888-967-5224Website: workaci.comCAUTION:DO NOT USE THIS PRODUCT IN ANY SAFETY RELATED APPLICATIONS WHERE HUMAN LIFEMAY BE AFFECTED.GENERAL INFORMATIONThe RD2432D is an output module that works with the MOD9200 series network transceivers to output four (4)analog 0-5 VDC/0-10 VDC and four (4) digital signals (dry contact) for wireless control of modulating actuators orwireless status indications. The network transceiver receives the wireless signal from the sensor/input concentratorand that data is sent to the BAS via RS-485. If the BAS determines an action is needed, it then sends the command tothe transceiver and the transceiver sends that command wirelessly to the RD2432D, which then outputs either ananalog or digital signal.Transmission distance in a typical building is 200-300 feet horizontal depending on the layout and construction ofthe building, and one floor above and one floor below the transceiver. Sensor distance and reliability can beincreased with the addition of a RR2552B(s) repeater.PRECAUTIONSSENSORS, REPEATERS AND RECEIVERS SHOULDNOT BE INSTALLED IN THE FOLLOWING AREAS:• INSIDE METAL ENCLOSURE / PANEL• INSIDE OR IMMEDIATELY NEXT TO ELEVATORSHAFT / ELEVATOR BANKS• IN FRONT OF OR IMMEDIATELY NEXT TO LARGETREES OR LARGE BODY OF WATERTRANSMISSION DISTANCE AND PERFORMANCEWILL BE DRASTICALLY REDUCED.MOUNTING INSTRUCTIONSMount the RD2432D output module as close to theequipment or controller as possible using four #8 screws(mounting dimensions see Figure 1). The maximumwiring distance for the analog outputs is 100 ft.WIRING INSTRUCTIONSWIRING PRECAUTIONS• Do NOT run Analog/Digital Output wires in anyconduit with line voltage (24/120/230 VAC).• Remove power before wiring. NEVER connector disconnect wiring with power applied.• The RD2432D is full wave rectified.• It is recommended that you use an isolatedUL-listed Class 2 transformer when powering theunit with 24 VAC. Failure to wire the devices withFIGURE 2: WIRELESS MULTILEVELDIAGRAMSENSORSENSORSENSORSENSORRECEIVER/REPEATER