FS-PP v2Fixture Mount Power PackInstallation Instructions FS-PP V2Model:Fixture Sensor Power Pack120/277/347VAC, 60Hz@120VAC 5A (N/O)3A (N/C)@277VAC 4.3A (N/O)2.5A (N/C)@347VAC 3.4A (N/O)2A (N/C)03392r2Strip GaugeAC INPUTSPECIFICATIONSPower .................................................120/277/347VAC, 60HzRelay Type ................. Form C with Zero Crossing on N.O. onlyOutput ........................ 70mA @ +24VDC with relay connectedLoad Requirements@120VAC.................................5.0A (N/O), 3.0A (N/C), 1/6hp@277VAC.................................4.3A (N/O), 2.5A (N/C), 1/6hp@347VAC............................................ 3.4A (N/O), 2.0A (N/C)Low Voltage Connections ....... RJ45 connection to FS sensors...................................... Control in, common, +24VDCLine and Load Connections...........12-18AWG screw terminalsTerminal Torque Rating ....4.428 inch pound-force (0.5Nm)Operating Temperature..................... 32° to 131°F (0° to 55°C)Dimensions .................... 7.5” x 0.87” x 1.0” (190 x 22 x 25mm)