Manual Corrigo Ventilation, revision R Chapter 17 Configuration 81After choosing AI or DI signal (the unused alternative must be set to not active) there are submenuswith settings. These menus are accessed by pressing RIGHT.UAI1Sign: SAF pressureRaw Value:8.5Compensation: 0.0UDI1NO/NC: NO SignalNot usedStatus: NoTo simplify adaptation to external functions, all universal inputs configured as digital inputs can beset to be either normally open, NO, or normally closed, NC.The inputs are as standard normally open, i. e. if the input is closed, the function connected to theinput in Corrigo is activated.Be careful when changing the input from NO to NC since some digital functions can be configuredto either NO or NC themselves. For example, you can choose if the Fire alarm input should beactivated when it is closed or opened. Therefore, there is a risk that the signal is changed twice andthe result is the opposite of the desired.17.1.4 Analogue outputsAnalogue outputs are 0…10 V DC.AO1Sign: Y1-HeatingAutoValue: 0.0 VAnalogue outputs can be set in run mode "Auto", "Manual" or "Off".17.1.5 Digital outputsDO1Signal: SAF 1/1-speedAutoStatus: OnDigital outputs can be set in run mode "Auto", "Manual-On" or "Manual-Off".17.2 Sensor settingsPT1000 setpoint devices can be connected to function as outdoor and room temperature sensors.Alternatively, 0...10 V transmitters can also be used.Room temp1Sensor type: PT1000If any of the sensors are set to 0...10 V, the sensor can be scaled using the right arrow key on thecontroller:Room temp10V = 0°C10V = 100°C