88 OI/266/PB-EN Rev. E | 2600T Series Pressure transmittersAppendix D – TroubleshootingAppendix D – Troubleshootingsym Error HMI code Description Possible Cause Suggested ActionsElectronics errorsMemory Failure F116.023 The device data loaded at the start up are corruptedprecluding the correct functionality of the device Electronic memory corrupted The electronics must be replacedElectronic Interface error. M030.020 Exchange of data between Electronics and Sensor haveproblemsExchange of non-critical data between sensor andelectronics is precluded due to problem in theelectronic circuit or in receiver circuit of the sensorPower the device and retry the operation,if the error persist the electronics shouldbe replaced as soon as possible.Non-Volatile memory burn error M026.024 The device continue to work without problems but at thenext power cycle the new configuration will be lostWritings to the electronic non-Volatile Memory wasnot successfulThe electronics should be replaced assoon as possible.Pressure Sensor errorsSensor InvalidMissing PrimarySignal F120.016The primary signal of the sensor is no longer available.The transducer is not in a condition to generate a validsignal.The sensor signal is not being updated correctly asa result of an electronics failure, sensor error or apoorly connected sensor cable.Check cable connection, check sensorand if problem persists, the sensor mustbe replaced.Invalid Sensor Sensor and/or the connected electronics areincompatibleThe sensor model/version is not longer compatiblewith the connected electronic version The sensor must be replacedSensor Memory Fail F118.017 The data in the sensor memory are corrupted precludingthe correct functionality of the device Sensor memory corrupted The Sensor must be replacedP-dP Sensor Fail F114.000 The sensor signal value is incorrect due to a mechanicalfailureMechanical damage to the sensor. Loss of fill fluid;ruptured diaphragm, broken sensor…. The Sensor must be replacedStatic Pressure Sensor Fail F112.001 The sensor signal value is incorrect due to a mechanicalfailure …… Valid only for Differential pressure modelsThe circuitry for the sampling of the static pressurehas failed. The Sensor must be replacedSensor Temperature Fail F110.002 The measurement accuracy is decreased more than theacceptable errorThe circuitry for the sampling of the temperaturehas failed. The Sensor must be replacedNon-Volatile memory burn error M028.018The device continue to work without problems but anyreplacement operation is compromised because theback-up configuration is not updatedWritings to the Sensor non-Volatile Memory wasnot successfulThe Sensor should be replaced as soon aspossible.Installation/start-up errorsInput SimulationActivePdP simulationC088.030The Process Value is simulated to became the P-dPvalue measured in inputThe P-dP Value in output is calculated from a valuesimulated in input Use a HART configurator (DTM - Handheld) to place device back into normaloperating mode (Remove the inputsimulation)Static PressuresimulationThe Process Value is simulated to became the StaticPressure value measured in inputThe Static Pressure Value in output is calculatedfrom a value simulated in inputSensor TempsimulationThe Sensor Temperature Value is simulated to becamethe measured Sensor Temperature valueThe Sensor Temperature Value in output iscalculated from a value simulated in input