Parameter Values (Range) Unit Step Default DescriptionPressure alarm time 0...60000 ms 1 10 Time delay for gas pressure alarm in msPres lockout time 0...60000 ms 10 10 Time delay for gas pressure lockout in msIni inactive days 0...9999 1 0 Initial value of the inactive days counterInactive Alm hours 0...23 h 1 0 Alarm time of the inactive days counter in hours7.1.8 Monitored dataTable 787:52CM Monitored dataName Type Values (Range) Unit DescriptionT_TRV_OP FLOAT32 0...60000 ms Travel time of the CB duringopening operationT_TRV_CL FLOAT32 0...60000 ms Travel time of the CB duringclosing operationT_SPR_CHR FLOAT32 0.00...99.99 s The charging time of the CBspringNO_OPR INT32 0...99999 Number of CB operation cycleINA_DAYS INT32 0...9999 The number of days CB hasbeen inactiveCB_LIFE_A INT32 -99999...99999 CB Remaining life phase ACB_LIFE_B INT32 -99999...99999 CB Remaining life phase BCB_LIFE_C INT32 -99999...99999 CB Remaining life phase CIPOW_A FLOAT32 0.000...30000.000Accumulated currents power(Iyt), phase AIPOW_B FLOAT32 0.000...30000.000Accumulated currents power(Iyt), phase BIPOW_C FLOAT32 0.000...30000.000Accumulated currents power(Iyt), phase C52CM Enum 1=Enabled2=blocked3=test4=test/blocked5=DisabledStatus1MAC059074-MB A Section 7Condition monitoring functions615 series ANSI 895Technical Manual