The internal fault code indicates the type of internal IED fault. When a fault appears, thecode must be recorded so that it can be reported to ABB customer service.Fault indication Fault code Additional informationInternal Fault System error 2 An internal system error hasoccurred.Internal Fault File system error 7 A file system error has occur-red.Internal Fault Test 8 Internal fault test activatedmanually by the user.Internal FaultSW watchdog error10 Watchdog reset has occurredtoo many times within an hour.Internal Fault License check fail 117 The devices is equipped withinvalid license.5.3.2 WarningsWarnings are shown in the event list of the WHMI. The text Warning additionally providedwith the name of the warning, a numeric code as well as the date and time is shown onthe WHMI. The warning indication message can be manually cleared.Note: If a warning appears, record the name and code so that it can beprovided to ABB customer service.Table 11: Warning indications and codesWarning indication Warning code Additional informationWarning IEC61850 error 20 Error when building the IEC61850 data model.Warning Dataset error 24 Error in the Data set(s).WarningReport cont. error25 Error in the Report controlblock(s).WarningGOOSE contr. error26 Error in the GOOSE controlblock(s).WarningSCL config error27 Error in the SCL configurationfile or the file is missing.Warning Logic error 28 Too many connections in theconfiguration.WarningSMT logic error29 Error in the SMT connections.WarningGOOSE input error30 Error in the GOOSE connec-tions.ACT error 31 Error in the ACT connections.WarningGOOSE Rx. error32 Error in the GOOSE messagereceiving.Troubleshooting 1MRS75885054 SSC600Operation Manual