Technical data 111 UL class T and L fusesDimensions, weights and free space requirementsW1 width of the basic unit with PE terminalW2 width with the cable connection terminal plates* Depth without fastening brackets is 568 mm (22.36 in.).Note 1. For more information on dimensions, see chapter Dimension drawings.Note 2. Different pedestal (flat type) and busbar sets are available. See page 25.Note 3. For free space requirements around the drive module, see page 39.Drive typeACS850-04…InputcurrentFuseA A V Manufacturer Type UL class-302A-4 297 500 600 Bussmann JJS-500 T-361A-4 355 500 600 Bussmann JJS-500 T-414A-4 407 500 600 Bussmann JJS-500 T-477A-4 459 600 600 Bussmann JJS-600 T-550A-4 531 800 600 Ferraz A4BY800 L-616A-4 599 800 600 Ferraz A4BY800 L-704A-4 689 800 600 Ferraz A4BY800 LNote 1: See also Implementing thermal overload and short-circuit protection on page 62.Note 2: In multicable installations, install only one fuse per phase (not one fuse per conductor).Note 3: Larger fuses than the recommended ones must not be used.Note 4: Fuses from other manufacturers can be used if they meet the ratings and the melting curve of thefuse does not exceed the melting curve of the fuse mentioned in the table.00581898IP00 UL type openHeight W1 W2 Depth* Weight Height W1 W2 Depth* Weightmm mm mm mm kg in. in. in. in. lb1564 415 562 571 200 61.57 16.35 22.14 22.48 441