49 COMPLETEPARAMETERSGroup 32: SupervisionParameters of this group are used together with relay output parameters1401 RELAY OUTPUT 1 and 1402 RELAY OUTPUT 2. Any two parameters of theOperating Data group (Group 1) can be supervised. Relays can beconfigured to be energised when the values of supervised parameters areeither too low or too high.Figure 14 Operating data supervision using relay outputs.Code Description3201 SUPERV 1 PARAMFirst supervised parameter number of the Operating Data group (Group 01).3202 SUPERV 1 LIM LOFirst supervision limit low. Display of this parameter depends on selected super-vised parameter (3201).3203 SUPERV 1 LIM HIFirst supervision limit high. Display of this parameter depends on selectedsupervised parameter (3201).3204 SUPERV 2 PARAMSecond supervised parameter number of the Operating Data group (Group 01).3205 SUPERV 2 LIM LOSecond supervision limit low. Display of this parameter depends on selectedsupervised parameter (3204).3206 SUPERV 2 LIM HISecond supervision limit high. Display of this parameter depends on selectedsupervised parameter (3204).HI (3203)LOW (3202)Value of supervised parameterenergised =1de-energised = 0energised =1de-energised = 0ABA = Parameter 1401 RELAY OUTPUT 1 (1402 RELAY OUTPUT 2) value isSUPRV 2 OVERB = Parameter 1401 RELAY OUTPUT 1 (1402 RELAY OUTPUT 2) value isSUPRV 2 UNDEROVER orSUPRV 1 UNDER orSUPRV 1