Actual signals and parameters 17ParametersAll parametersNo. Name/Value Description Def/FbEq11 REFERENCESELECTPanel reference type, external control location selection andexternal reference sources and limits1104 REF1 MIN Defines the minimum value for external reference REF1.Corresponds to the minimum setting of the used sourcesignal.0.0 Hz /1 rpm0.0…1400.0 Hz/ 0…32000 rpmMinimum value in rpm. Hz if parameter 9904 MOTOR CTRLMODE setting is SCALAR: FREQ.Example: Analog input AI1 is selected as the referencesource (value of parameter 1103 is AI1). The referenceminimum and maximum correspond to the 1301 MINIMUMAI1 and 1302 MAXIMUM AI1 settings as follows:1 = 0.1 Hz/ 1 rpm1105 REF1 MAX Defines the maximum value for external reference REF1.Corresponds to the maximum setting of the used sourcesignal.E: 50.0 HzU: 60.0 Hz0.0…1400.0 Hz/ 0…32000 rpmMaximum value in rpm. Hz if parameter 9904 MOTORCTRL MODE setting is SCALAR: FREQ. See the examplefor parameter 1104 REF1 MIN.1 = 0.1 Hz/ 1 rpm12 CONSTANTSPEEDSConstant speed selection and values.1202 CONSTSPEED 1Defines constant speed (or drive output frequency) 1. E: 5.0 HzU: 6.0 Hz0.0…1400.0 Hz/ 0…32000 rpmSpeed in rpm. Output frequency in Hz if parameter 9904MOTOR CTRL MODE setting is SCALAR: FREQ.1 = 0.1 Hz/ 1 rpm1203 CONSTSPEED 2Defines constant speed (or drive output frequency) 2. E: 10.0 HzU: 12.0 Hz0.0…1400.0 Hz/ 0…32000 rpmSpeed in rpm. Output frequency in Hz if parameter 9904MOTOR CTRL MODE setting is SCALAR: FREQ.1 = 0.1 Hz/ 1 rpm1204 CONSTSPEED 3Defines constant speed (or drive output frequency) 3. E: 15.0 HzU: 18.0 HzREF (Hz/rpm)REF1 MAX(1105)REF1 MIN(1104)-REF1 MIN(1104)-REF1 MAX(1105)AI1 signal (%)1302 13011301 1302