Technical data 107Motor connection dataMotor type Asynchronous induction motor or permanentmagnet synchronous motorVoltage (U2 ) 0 to U1 , 3-phase symmetrical, Umax at the field weakening pointShort-circuit protection(IEC 61800-5-1,UL 61800-5-1)The motor output is short-circuit proof by IEC 61800-5-1 andUL 61800-5-1.Frequency (f2) 0…599 HzFrequency resolution 0.01 HzCurrent See Ratings on page 88.Switching frequency 2, 4, 8 or 12 kHz Motor cablelengthOperational functionality and motor cable lengthThe drive is designed to operate with optimum performance with thefollowing maximum motor cable lengths. The motor cable lengths maybe extended with output chokes as shown in the table.Note: In multimotor systems, the calculated sum of all motor cable lengthsmust not exceed the maximum motor cable length given in the table.FramesizeMaximum motor cable lengthm ftStandard drive, without external optionsR0 150 492R1, R2 150 492R3, R4 150 492With external output chokesR0 60 195R1…R3 250 820R4 200 656