34 Program featuresNote: The ramp shape time is set to zero during jogging.Load analyzer Peak value loggerThe user can select a signal to be monitored by the peak value logger. The loggerrecords the peak value of the signal along with the time the peak occurred, as well asmotor current, DC voltage and motor speed at the time of the peak. Amplitude loggersThe user can select a signal to be sampled at 200 ms intervals when the drive isrunning, and specify a value that corresponds to 100%. The collected samples aresorted into 10 read-only parameters according to their amplitude. Each parameterrepresents an amplitude range 10 percentage points wide, and displays thepercentage of the collected samples that fall within that range.There is also an amplitude logger 1 which is fixed to monitor motor current. Amplitudelogger 1 cannot be reset.SettingsParameter group 64 Load analyzer (page 188).Percentage of samples0…10%10…20%20…30%30…40%40…50%50…60%60…70%70…80%80…90%>90%Amplitude ranges(parameters 64.24…64.33)