Technical data117Losses, cooling data and noiseIP22 cabinet with no extra fanAn IP22 cabinet should meet the following data to ensure efficient cooling of thedrive module. No extra fan is used. The pressure drop over the cabinet is theadditional counterpressure that the module fan is capable of overcoming while stillmaintaining the required air flow through the module.IP54 cabinet with an extra fanAn IP54 cabinet should meet the following data to ensure efficient cooling of thedrive module. An extra fan is used. The pressure drop over the cabinet is thecounterpressure the extra fan must overcome. The given fan types and filtermaterials are examples. Corresponding products by another manufacturer may beused as well. See the manufacturerís Internet site for the detailed specification.Drive typeACS850-04ÖFramesizeAir flow Heat dissipation Noisem3/h ft 3 /min W BTU/Hr dB-430A-5 R8 1220 718 6850 22550 72-521A-5 R8 1220 718 7800 24420 72-602A-5 R8 1220 718 7600 27670 72-693A-5 R8 1220 718 8100 29550 72-720A-5 R8 1220 718 9100 31080 72Temperature rise overmodule30 ∞CPressure drop 300 Pa (over module), 45 Pa over cabinetCabinet air inlet Minimum size (mm): 288◊292+688◊521Filter by Luftfilter: airTex G150Cabinet air outlet size 398 mm ◊ 312 mm (2 pcs) when the outlet is located on the cabinet roof00096931Temperature rise overmodule30 ∞CPressure drop 250 Pa (over cabinet), average, air filters moderately congestedExtra fan type RH35M-4EK.2F.1R by Ziehl-Abegg or RB4T-355/170 by ebmAir inlet filter by Luftfilter airComp 300-50,Minimum size in door (mm): 288◊292 + 688◊521Air outlet filter byLuftfilterairTex G150Minimum size at roof (mm): 398◊312 (2 pcs)00096931Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com