CMS-700 SYSTEM CIRCUIT MONITORING SYSTEM (CMS)33—WEB UI - Settings Menu—Settings Menu - EventsThis page allows to set events. If an event occurs, it is shown in the historical events menu. An event canoccur after exceeding the selected threshold values (cross-up) or after measuring values lower than theselected threshold values (cross-down) for a determined period (time delay). The email report is sentafter 1 minute from the first event occurance and consists of all events that occured in this period. Thenext report can only be sent after at least 30 minutes since the first event occurance and only in caseevent conditions are still ongoing.When adding a new event, please set the following:Mains/Branches Select whether the event shall be created for mains or branchesOwner Select main line or the branch name. For branches it is possible to create thesame event for several branches by selecting “Add many” option.Value It identifies the quantity to which the event is linkedType Type of alarm: Cross-up, Cross-down or No eventThreshold Threshold of selected valueTime delay Define for how long the event criteria should be fulfilled in orderto consider the occurrence as an eventEmail If the box is selected, an e-mail will be sent.The email address has to be defined in “Settings – Email, FTP”.