DescriptionValue or Value range/ DefaultProperty / Para-meterDefines the delay after which the receiverof line is enabled after a message hasbeen issued.0...255Receive InterruptDelayThe time that IEC link waits for the end ofthe received message in seconds.0...255Default: 2Response TimeoutThe number of characters for calculatingdelay for resetting RTS signal.0...20Default: 1RTS Keep Up DelayThe number of padding characters inser-ted to the end of telegram to delay theresetting of RTS signal.0...255Default: 0RTS Keep Up Pad-ding CharactersTime synchronization interval in seconds.0...65535Default: 15Time Synchroniza-tion IntervalDelay in milliseconds between receivingCTS signal and start of transmission.0...65535Default: 15Transmission WaitDelayPollingDelay between polling messages.0...65535Default: 50Polling DelayLimits the number of successive polls ofstation.2...100Default: 10Polling LimitThe polling frequence of suspended sta-tion.1...255Default: 10Polling PeriodThe reply polling specifies the number ofsuccessive polls to a station where com-mand has been sent.1...20Default: 1Reply Poll CountLimits the number of successive class 2polls of station. Value should be smallerthan value of Polling Limit.0...100Default: 0Secondary PollingLimitConfiguring IEC101 Device properties3.4.4.Table 3.4.4-1 lists the configurable properties for IEC101 Device and value ranges forthese properties. The actual configuration by using SAB600 is performed as describedin 3.4.1, General about configuring objects.Table 3.4.4-1 IEC101 Device propertiesDescriptionValue/Value rangeNameBasic27IEC 60870-5-101Master (OPC) 3.3Station Automation COM6001MRS756703User's Manual