To reconfigure Configuration Service from WebHMI:• Click SetRemotingParameters shortcut on COM600 desktop. COM600 RemotingSettings window opens.• Select the new IP address of the LOCAL NIC and click Apply.• Verify that the change reflects in Current IP and Port number.Remote desktop3.2.5.Windows remote desktop application in COM600 can be used to perform any maintenanceactivities on COM600. These activities may involve managing for example any OSrelated configuration, files/folder in hard drive, or network configuration. COM600 canbe made available for remote connection from peer Windows devices located outsideits physical perimeter by connecting it to a REMOTE LAN.Before using Windows remote desktop application, the remote settings in COM600should be enabled to allow remote desktop connections. This can be done using COM600WebHMI. ABB recommends that remote desktop connections are enabled only whenneeded.To configure Remote desktop settings from WebHMI:1. Login to COM600 WebHMI with a user account that has administrative privileges.2. Select Communication tab.3. Click Security Settings node in the tree displayed.4. Select Remote desktop child node.5. Selecta. Allow connections / Allow only secure connections option to enable remotedesktop connection to COM600.b. Don’t allow connections to COM600 computer option to disable remotedesktop connection to COM600.6. Click Apply.Enable_Remote_Desktop.pngFigure 3.2.5-1 Enable Remote Desktop Connection23COM600 series 5.01MRS758267Cyber Security Deployment Guideline