ReportClientFigure 3.4.4-3 Adding ReportClient objects4. Configure the report control block.5. Configure the data set of the report control block.data_set_propertiesFigure 3.4.4-4 Data set propertiesGOOSE messaging3.4.5.The generic object oriented substation event (GOOSE) is used in substation automationfor fast horizontal communication between IEDs. It can be used to exchange, for example,interlocking and blocking information. The information is shared from one IED to oneor several IEDs using Ethernet multicast messages. A message is an image of a sentMMS data set that is defined in the CID configuration.25COM600 series, version 4.11MRS757275IEC 61850 Proxy Server User's Manual