44PU.SCALEtYPE20.0OUtPUtrEt–HI4.0rEt–LOAdJUStrEtrAN4.12 Retransmission Output PageInformation.• Retransmission of process variable, set point, control output or position feedback input.• Programmable current output range.• Retransmission output can be used for cool output in heat/cool applications.…4 CONFIGURATIONPage Header – Retransmisson Output.Parameter TypeSelect the parameter type to be re-transmitted, PV(process variable input), SPt (set point), OUt (output) orPFb (position feedback).Retransmission MaximumSet the maximum retransmission value, between 0.0mAand 20.0mA in 0.1mA increments.Retransmission MinimumSet the minimum retransmission value, between 0.0mAand 20.0mA in 0.1mA increments.Return to top of Retransmission Output PageorAdvance to Scale Adjustment Page.Page Header – Cool Output PageCool Output MaximumSet the maximum value for the cool output, between0.0mA and 20.0mA in 0.1mA increments.Cool Output MinimumSet the minimum value for the cool output, between 0.0mAand 20.0mA in 0.1mA increments.Return to top of Cool Output Pageoradvance to Scale Adjustment Page.4.13 Cool Output PageThis page is only present if HtCOOL is selected at Control Mode and C-ProP is selected atSecond Output Type in the Set Up Control Page – see Fig. 3.1 and Section 4.10.OUtPUtSCALE20.0COOL–HICOOL4.0COOL–LOAdJUSt