ControlMaster CM10, CM30 and CM50Universal process controllers, 1/ 8 , 1/ 4 and 1 /2 DIN 4 Installation14 IM/CM/S–EN Rev. R4.5 Electrical ConnectionsWarning. The controller is not fitted with a switch therefore a disconnecting device such as a switch or circuit breaker conforming to local safetystandards must be fitted to the final installation. It must be mounted in close proximity to the controller within easy reach of the operator and must be marked clearly as the disconnectiondevice for the instrument. Remove all power from supply, relay and any powered control circuits and high common mode voltages before accessing or making anyconnections. Use cable appropriate for the load currents. The terminals accept cables from 18 to 14 AWG (0.8 to 2.5mm2 ). Always route signal leads and power cables separately, preferably in earthed (grounded) metal conduit. It is strongly recommended that screened cable is used for signal inputs and relay connections. The instrument conforms to Mains Power Input Overvoltage Category 2, Pollution Degree 2 (EN601010–1).(This equipment is protected through double insulation – Insulation Class II.) Analog / digital inputs and outputs, transmitter power supply and DC power supply are SELV (Safety Extra Low Voltage) circuits. All connections to secondary circuits must have basic insulation. After installation, there must be no access to live parts, e.g. terminals. Terminals for external circuits are for use only with equipment with no accessible live parts. If the controller is used in a manner not specified by the Company, the protection provided by the equipment may be impaired. All equipment connected to the controller's terminals must comply with local safety standards (IEC 60950, EN601010–1).Note. Terminal screws must be tightened to a torque of 0.1 Nm (0.9 lbf/in.).