Electrical connection42/68-831-EN EBS852, EBS862 (Contrac) 19Pos: 12.4 /Überschriften/1.1/1-spaltig/A - C/Antriebszuordnung und Leitungsquerschnitte @ 20\mod_1209547381234_3101.doc @ 1831675.1 Actuator assignment and cable cross-sectionsPos: 12.5 /Elektrischer Anschluss/Aktorik/Antriebe/Leistungselektroniken/EBS852, EBS862/Antriebszuordnung/Leitungsquerschnitte Schwenkantriebe Ex @ 20\mod_1209543500093_3101.doc @ 1831105.1.1 Rotary actuatorsMax. currentconsumption 1)Motor cable cross-section / Permissible cable length inm (ft) 2)ElectronicunitAverage powerloss of theelectronic unit115 V 230 VActuator1.5 mm 2(16 AWG)2.5 mm 2(14 AWG)4 mm 2(12 AWG)6 mm 2(10 AWG)10 mm 2(8 AWG)60 W 1.8 A 0.9 A RHDE250-1075 W 2.2 A 1.1 A RHDE500-1060 W 5.0 A 2.5 A RHDE800-1080 W 5.0 A 2.5 A RHDE1250-1280 W 5.0 A 2.5 A RHDE2500-2580 W 5.8 A 2.7 A RHDE4000-40EBS85280 W 5.0 A 2.5 A RHDE8000-8080 W - 5.3 A RHDE2500-10270(866)460(1476) - - -100 W - 10.0 A RHDE4000-10 160(513)270(866)430(1380) - -115 W - 8.0 A RHDE8000-15EBS862On request - 12.5 A RHDE16000-3070(225)120(385)190(610)280(898)460(1476)1) At actuator rated power. Current consumption in positioning mode approx. 40 ... 50 % of l max in each case.2) Cable length between electronic unit and actuator. Signal cable cross-section 0.5 mm 2 (20 AWG).Pos: 12.6 /Elektrischer Anschluss/Aktorik/Antriebe/Leistungselektroniken/EBS852, EBS862/Antriebszuordnung/Leitungsquerschnitte Linearantriebe Ex @ 20\mod_1209546356437_3101.doc @ 1831435.1.2 Linear actuatorsMax. currentconsumption 1)Motor cable cross-section / Permissible cable length inm (ft) 2)ElectronicunitAverage powerloss of theelectronic unit115 V 230 VActuator1.5 mm 2(16 AWG)2.5 mm 2(14 AWG)4 mm 2(12 AWG)6 mm 2(10 AWG)10 mm 2(8 AWG)55 W 2.2 A 1.1 A RSDE10-5.060 W 3.6 A 1.8 A RSDE10-10,060 W 3.6 A 1.8 A RSDE20-5.075 W 4.8 A 2.4 A RSDE20-7.5EBS85275 W 5.0 A 2.5 A RSDE50-3.0270(866)460(1476) - - -EBS862 100 W - 6.4 A RSDE50-10.0 160(513)270(866)430(1380) - -1) At actuator rated power. Current consumption in positioning mode approx. 40 ... 50 % of l max in each case.2) Cable length between electronic unit and actuator. Signal cable cross-section 0.5 mm 2 (20 AWG).Pos: 12.7 /======= Seitenumbruch ======== @ 0\mod_1126532365768_3101.doc @ 3830