ABB SACE 23The Power Center MNS R switchgear have been tested accordingto relevant IEC standards, among which the following stand out:– Test report n° 100310: Short-circuit 50 kA 1s– Test report n° 100397: Short-circuit 75 kA 1s– Test report n° 100398: Short-circuit 100 kA 1s– Test report LBRP n° 5193: Arc-proof 50 kA 0.3 s 726 V– Test report LBRP n° 5203: Arc-proof 75 kA, 0.5 s 726 V– Test report n° 0117/B: verification of temperature rise limits3000/5000 A– Test report LOVAG-ACAE n° IT 01.044: verification oftemperature rise limits (6300 A) and verification of dielectricproperties (Uimp = 12 kV)Tests and certifications