FEP630, FEH630 ELECTROMAGNETIC FLOWMETER | OI/FEP630/FEH630-EN REV. D 55Parameterization via the infrared service port adapterConfiguration via the infrared service port adapter on the devicerequires a PC / notebook and the FZA100 infrared service portadapter.By combining the HART-DTM and the software ‘flow’ available atwww.abb.com/ABB AssetVision, all parameters can also be setwithout a HART connection.G11911RxDTxD3211 Infrared service port adapter2 USB-interface cable3 PC / Notebook running ABBAssetVision and HART DTMFigure 72: Infrared service port adapter on the transmitter (example)1. Position the infrared service port adapter on the front plateof the transmitter as shown2. Insert USB interface cable into a free USB female connectoron the PC / notebook.3. Switch on the device power supply.4. Start ABB AssetVision and perform the parameterization ofthe equipment.Detailed information on operating the software is available inthe relevant operating instructions and the DTM online help.Parameterization via HART®Configuration via the HART interface of the device requires aPC / Notebook and a suited HART® Modem.All parameters can also be set via the HART protocol, using theHART DTM available at www.abb.com/flow and theABBAssetVisionsoftware.G119121~4 ... 20 mA / HART231 PC / Notebook running ABBAssetVision and HART DTM2 HART modem3 Power supply unitFigure 73: HART Modem on the transmitter (example)For more detailed information on operating the software andthe HART modem, please refer to the relevant operatinginstructions and the DTM online help.