1MRK 505 353-UEN Section 3Configuring bay protection using HMI500Application Manual 29Bay protection functions REB5003.4.2 Configuring binary output signalsEach REB500 bay protection function has a defined number of binary output sig-nals. These are described for each of the protection functions in Section 2.3.2.4. Inthe dialogs for setting protection functions, a binary output signal is described inplain text and has a field, which lists the input signals assigned to the respectiveoutput.Figure 15 BP output signal assignmentThe list shows the input signals assigned to the respective output. For each signalin the list, the instance number and an abbreviation of the function are given.Table 42 BP output signal assignmentExample Description09 Instance of BP functionOR Symbol representing the BP function of the instanceBinary Inp 2 Binary input 2 of OR functionOutput signals are assigned when configuring either the binary out-put function (see Section 3.4.2.1) or bay protection input signalfunction (see Section 3.4.1.1).3.4.2.1 Exception: Binary output functionThe binary output function has to be included in all sets of parameters and that iswhy the function is automatically selected for all of them and the setting cannot bechanged by the user.Figure 16 Parameter set assignment of BP outputs (fixed allocation)