3.4.2 FunctionsTable 8:Functions included in the standard configuration AFunctionality IEC 61850 IEC 60617 IEC-ANSIProtectionThree-phase non-directional overcurrentprotection, low stage, instance 1 PHLPTOC1 3I> (1) 51P-1 (1)Three-phase non-directional overcurrentprotection, high stage, instance 1 PHHPTOC1 3I>> (1) 51P-2 (1)Three-phase non-directional overcurrentprotection, high stage, instance 2 PHHPTOC2 3I>> (2) 51P-2 (2)Three-phase non-directional overcurrentprotection, instantaneous stage, instance 1 PHIPTOC1 3I>>> (1) 50P/51P (1)Negative-sequence overcurrent protection,instance 1 NSPTOC1 I2> (1) 46 (1)Negative-sequence overcurrent protection,instance 2 NSPTOC2 I2> (2) 46 (2)Binary signal transfer BSTGGIO1 BST BSTLine differential protection and relatedmeasurements, stabilized andinstantaneous stagesLNPLDF1 3dI>L 87LCircuit breaker failure protection CCBRBRF1 3I>/Io>BF 51BF/51NBFThree-phase inrush detector INRPHAR1 3I2f> 68Master trip, instance 1 TRPPTRC1 Master Trip (1) 94/86 (1)Master trip, instance 2 TRPPTRC2 Master Trip (2) 94/86 (2)ControlCircuit-breaker control CBXCBR1 I <-> O CB I <-> O CBDisconnector position indication, instance 1 DCSXSWI1 I <-> O DC (1) I <-> O DC (1)Disconnector position indication, instance 2 DCSXSWI2 I <-> O DC (2) I <-> O DC (2)Disconnector position indication, instance 3 DCSXSWI3 I <-> O DC (3) I <-> O DC (3)Earthing switch indication ESSXSWI1 I <-> O ES I <-> O ESCondition monitoringTrip circuit supervision, instance 1 TCSSCBR1 TCS (1) TCM (1)Trip circuit supervision, instance 2 TCSSCBR2 TCS (2) TCM (2)Current circuit supervision CCRDIF1 MCS 3I MCS 3IProtection communication supervision PCSRTPC1 PCS PCSMeasurementDisturbance recorder RDRE1 - -Three-phase current measurement,instance 1 CMMXU1 3I 3ISequence current measurement CSMSQI1 I1, I2, I0 I1, I2, I03.4.2.1 Default I/O connectionsSection 3 1MRS756498 DRED615 standard configurations28 RED615Application Manual