The scale factor is calculated as follows:(3277.0 2.0 ) 0.1 and 0.065535.0scalefactor offset´= = =IECEQUATION2447 V1 ENThe scale factor will be sent as 1 on configuration frame 2, and 0.1 on configurationframe 3. The range of analog values that can be transmitted in this case is -0.1 to-3276.8 and +0.1 to +3276.7.Example 2:4915.5AnalogXRange =IECEQUATION2448 V1 ENThe scale factor is calculated as follows:(4915.5 2.0 ) 0.15 a nd 0.065535.0sc alefac tor offse t´= = =IECEQUATION2449 V1 ENThe scale factor will be sent as 1 on configuration frame 2, and 0.15 on configurationframe 3. The range of analog values that can be transmitted in this case is -0.15 to-4915.5 and +0.15 to +4915.5.Example 3:10000000000AnalogXRange =IECEQUATION2450 V1 ENThe scale factor is calculated as follows:(10000000000 2.0) 305180.43 and 0.065535.5scalefactor offset´= = =IECEQUATION2451 V1 ENThe scale factor will be sent as 3051804 on configuration frame 2, and 305180.43 onconfiguration frame 3. The range of analog values that can be transmitted in this case is-305181 to -10000000000 and +305181 to +10000000000.6.2.3.4 PMU Report Function Blocks Connection Rules in PCM600 ApplicationConfiguration Tool (ACT)There are 3 important general rules which have to be considered in PCM600 ACT forthe connection of preprocessor blocks (SMAI) and 3PHSUM blocks toPHASORREPORT blocks:Rule 1:1MRK 502 071-UEN - Section 6Wide area measurement systemGenerator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062 115Application manual