2.3.1.88 LD0.XRGGIO130 Alarm/warningTable 91:LD0.XRGGIO130 Alarm/warningBitA RegA IEC 61850 name SA name Description ValuesLD0.XRGGIO1303072 192.00 .Alm.stVal - XRGGIO130 Alarm 1=Alarm3073 192.01 .mcd3074 192.02 .Wrn.stVal - XRGGIO130 Warning 1=Warning3075 192.03 .mcd2.3.2 Unmapped indicationsUnmapped indications are indication data that have no initial Modbus mapping locations,but can be added to the user-definable Modbus area using the CommunicationManagement tool in PCM600. If Modbus events are enabled for these indication signals,the event identification is the user-definable area address.2.3.2.1 All premapped three-phase protection function stages, trip/phase-dependent objects addedTable 92:All premapped three-phase protection function stages, trip/phase-dependent objects addedBitA RegA IEC 61850 name SA name Description ValuesLD0.xxxxxxxx (various).Op.phsA Phs A trip 1 = Trip.mcd.Op.phsB Phs B trip 1 = Trip.mcd.Op.phsC Phs C trip 1 = Trip.mcd2.3.2.2 Common data 2Table 93:Common data 2BitA RegA IEC 61850 name SA name Description ValuesLD0.LDEV1.StLstOv.stVal Internal ind. overflow 1=Overflow.mcd.MeasLstOv.stVal Internal meas. overflow 1=OverflowTable continues on next page1MAC252756-MB B Section 2Modbus data mappingsREM615 ANSI 57Point List Manual