Text Unit Default Min Max StepIntegration 0/1 0 0 1 1BinaryInp BinaryAddr Always offBlockInp BinaryAddr Always offTrip SignalAddrStart SignalAddr5.12.5 Parameters GUID-40CF9957-9979-46E5-8B57-8FA43FF48AD7 v1Table 96: Delay function - ParametersSignal DescriptionParSet 4..1 Parameter for determining in which set of parameters a particular function is active.Trip-Delay Time between start signal at the input and the tripping signal at the output.Reset-Delay Time required for the timer to reset after the input signal has disappeared.Integration Determination of the response of the function in the presence of a pulsating inputsignal:• 0: The delay continues to run, providing the input signal does not disappear forlonger than the reset time.• 1: The time during which the input is at logical 1 is integrated, that is, trippingdoes not take place until the sum of logical 1 time equals the set delay time.BinaryInp Timer input• xx: all binary inputs (or outputs of protection functions)BlockInp Input for blocking the function• F: enabled• T: disabled• xx: all binary inputs (or outputs of protection functions)Trip Tripping signalStart Pick-up signalSection 5 1MRK 505 406-UEN BBay protection functions176 Bay protection functions REB500Technical manual© Copyright 2019 ABB. All rights reserved