194.1.5. SubmenuThe menu structure contains several subgroups. The name of the main menu groupis always shown on the first line. The second line displays either the name of thegroup menu, the name of the parameter and the parameter value, or just theparameter value, in which case it is also the name of the parameter.* *#!!+)())A070062Fig. 4.1.5.-1 Display showing the first submenu* Enter a submenu by pressing ; exit by pressing .* Navigate between the main levels in the submenus by using or .* Press to return the display to the idle mode.4.1.6. HMI passwordsThe HMI passwords are used to protect user-changeable values on technical levelfrom being changed by an unauthorized person. There are two different HMIpasswords; an HMI setting password for changing all user-changeable values and anHMI communication password for changing communication settings only. Thepassword function remains inactive until the default password is replaced. Thedefault HMI password is 999. You can also change the HMI passwords via SPAparameters V162 and V163, but you can only read the password via the HMI.As soon as you have replaced the default HMI password, the new password isrequired for altering parameter values. Once you have given the valid password, thedisplay remains in the setting mode until returned to the idle mode.The following rules and exceptions apply, if the HMI passwords are in use:* Navigating and reading parameter values do not require a password.* All user-changeable values can be changed with the HMI setting password.* User-changeable values under CONFIGURATION\COMMUNICATION can bechanged either with the HMI communication password or the HMI settingpassword.* Changing of the SPA password requires the HMI setting password.* Changing of the HMI language does not require a password.* Setting of time and date does not require a password.* Performing trip lockout reset does not require a password.& ,- ')))!!"#$A040230_2Fig. 4.1.6.-1 HMI setting password request for editing setting parametersMotor Protection RelayOperator's Manual - ANSI versionREM 610REM 6101MRS755538