For each of the 352 signals, it is also possible to select if the signal is to be used asa trigger for the start of the Disturbance report and if the trigger should be activatedon positive (1) or negative (0) slope.OperationN: Disturbance report may trig for binary input N (On) or not (Off).TrigLevelN: Trig on positive (Trig on 1) or negative (Trig on 0) slope for binaryinput N.Func103N: Function type number (0-255) for binary input N according toIEC-60870-5-103, that is, 128: Distance protection, 160: overcurrent protection,176: transformer differential protection and 192: line differential protection.Info103N: Information number (0-255) for binary input N according toIEC-60870-5-103, that is, 69-71: Trip L1-L3, 78-83: Zone 1-6.See also description in the chapter IEC 60870-5-103.15.6.3.3 Analog input signals M12179-92 v5Up to 40 analog signals can be selected among internal analog and analog inputsignals. PCM600 is used to configure the signals.For retrieving remote data from LDCM module, the Disturbancereport function should be connected to a 8 ms SMAI function blockif this is the only intended use for the remote data.The analog trigger of Disturbance report is not affected if analog input M is to beincluded in the disturbance recording or not (OperationM = On/Off).If OperationM = Off, no waveform (samples) will be recorded and reported ingraph. However, Trip value, pre-fault and fault value will be recorded and reported.The input channel can still be used to trig the disturbance recorder.If OperationM = On, waveform (samples) will also be recorded and reported ingraph.NomValueM: Nominal value for input M.OverTrigOpM, UnderTrigOpM: Over or Under trig operation, Disturbance reportmay trig for high/low level of analog input M (On) or not (Off).OverTrigLeM, UnderTrigLeM: Over or under trig level, Trig high/low level relativenominal value for analog input M in percent of nominal value.15.6.3.4 Sub-function parameters M12179-389 v3All functions are in operation as long as Disturbance report is in operation.1MRK 506 375-UEN A Section 15MonitoringRailway application RER670 2.2 IEC 401Application manual