Table 63. Large displayCharacter size1) Rows in the view Characters per rowSmall, mono-spaced (6x12 pixels) 10 20Large, variable width (13x14 pixels) 8 8 or more1) Depending on the selected language19. Mounting methodsBy means of appropriate mounting accessoriesthe standard IED case for the 615 series IED canbe flush mounted, semi-flush mounted or wallmounted. The flush mounted and wall mountedIED cases can also be mounted in a tilted position(25°) using special accessories.Further, the IEDs can be mounted in any standard19” instrument cabinet by means of 19” mountingpanels available with cut-outs for one or twoIEDs. Alternatively, the IED can be mounted in 19”instrument cabinets by means of 4U Combiflexequipment frames.For the routine testing purposes, the IED casescan be equipped with test switches, type RTXP18, which can be mounted side by side with theIED cases.Mounting methods:• Flush mounting• Semi-flush mounting• Semi-flush mounting in a 25° tilt• Rack mounting• Wall mounting• Mounting to a 19" equipment frame• Mounting with a RTXP 18 test switch to a19" rackPanel cut-out for flush mounting:• Height: 161.5±1 mm• Width: 165.5±1 mm48177160177153164IECA070900 V4 ENFigure 15. Flush mounting98177160186103IECA070903 V4 ENFigure 16. Semi-flush mounting23010725°133190IECA070902 V4 ENFigure 17. Semi-flush with a 25ºtiltTransformer Protection and Control 1MRS756891 FRET615Product version: 4.0ABB 51