12.1.4.1 Setting examples SEMOD54481-4 v4Three setting examples, in connection to Measurement function (CVMMXN), are provided:• Measurement function (CVMMXN) application for a OHL• Measurement function (CVMMXN) application on the secondary side of a transformer• Measurement function (CVMMXN) application for a generatorFor each of them detail explanation and final list of selected setting parameters values will beprovided.The available measured values of an IED are depending on the actual hardware(TRM) and the logic configuration made in PCM600.Measurement function application for a 110kV OHL SEMOD54481-12 v10Single line diagram for this application is given in figure 80:110kV Busbar110kV OHLP Q600/1 A110 0,1/3 3 kVIEC09000039-2-en.vsdIEDIEC09000039-1-EN V2 EN-USFigure 80: Single line diagram for 110kV OHL applicationIn order to monitor, supervise and calibrate the active and reactive power as indicated infigure 80 it is necessary to do the following:1. Set correctly CT and VT data and phase angle reference channelPhaseAngleRef usingPCM600 for analog input channels2. Connect, in PCM600, measurement function to three-phase CT and VT inputs3. Set under General settings parameters for the Measurement function:• general settings as shown in table 23.• level supervision of active power as shown in table 24.• calibration parameters as shown in table 25.1MRK 505 355-UEN A Section 12Monitoring207Application manual