Headline ExplanationTime diff: IED vs Sampled value Identifier>Where the Hardware Module Identifier is thesame as given in PCM600, e.g. AP1: MU1_9201svID: Frequency diff: IED vs Sampled value Identifier>Where the Hardware Module Identifier is thesame as given in PCM600, e.g. AP1: MU1_9201svID: Invalid phase angle reference The selectedPhaseAngleRef corresponds to ananalog channel that is not configured. Pleaseconfigure a valid reference channel.GOOSE is configured on a disabled port At least one of the access points configured forGOOSE is disabled. The port can be disabledeither through changing the access pointoperation to off or by unchecking the GOOSEprotocol from the access point in the Ethernetconfiguration in PCM600 or LHMI.Please enable GOOSE on access points:AP_FRONT, AP_1LDCM not running the application image is running the factory imageinstead of the application image. The factoryimage is older and does not contain the latestupdates and fixes.Please reboot the IED. If the problem persistsupdate the LDCM firmware or replace the board.LDCM version is not accepted firmware version string> is not accepted. The minimum acceptedversion is .Please update the LDCM firmware or replace theboard.8.2 Indication messages8.2.1 Internal faults GUID-2ACAE73F-9CDD-4C33-AFED-6BACC8990F37 v7When the Ready LED indicates an internal fault by flashing, the messageassociated with the fault is found in the internal event list in the LHMI menu Mainmenu/Diagnostics/Internal events. The message includes the date, time,description and signal state for the fault. The internal event list is not updateddynamically. The list is updated by leaving the Internal events menu and thenselecting it again. The current status of the internal fault signals can also bechecked via the LHMI in Main menu/Diagnostics/IED status.Different actions are taken depending on the severity of the fault. If the fault isfound to be permanent, the IED stays in internal fault mode. The IED continues toperform internal tests during the fault situation.When a fault appears, the fault indication message is to be recorded and statedwhen requesting support or service.Section 8 1MRK 500 128-UEN BTroubleshooting78 650 series 2.2 IECOperation manual PreviousNext |