18.2.2 Horizontal communication via GOOSE for interlockingGOOSEINTLKRCV SEMOD173197-1 v2PID-415-SETTINGS v5Table 44: GOOSEINTLKRCV Non group settings (basic)Name Values (Range) Unit Step Default DescriptionOperation DisabledEnabled- - Disabled Operation Disabled/Enabled18.2.3 Setting guidelines SEMOD55317-5 v6There are two settings related to the IEC 61850–8–1 protocol:Operation User can set IEC 61850 communication toEnabled orDisabled.GOOSE has to be set to the Ethernet link where GOOSE traffic shall be send and received.18.2.4 Generic communication function for Single Point indicationSPGAPC, SP16GAPC SEMOD55999-1 v418.2.4.1 Application SEMOD55350-5 v6Generic communication function for Measured Value (SPGAPC) function is used to send one singlelogical output to other systems or equipment in the substation. It has one visible input, thatshould be connected in ACT tool.18.2.4.2 Setting guidelines SEMOD55376-5 v4There are no settings available for the user for SPGAPC. However, PCM600 must be used to get thesignals sent by SPGAPC.18.2.5 Generic communication function for Measured Value MVGAPCSEMOD55402-1 v318.2.5.1 Application SEMOD55872-5 v9Generic communication function for Measured Value MVGAPC function is used to send theinstantaneous value of an analog signal to other systems or equipment in the substation. It canalso be used inside the same IED, to attach a RANGE aspect to an analog value and to permitmeasurement supervision on that value.18.2.5.2 Setting guidelines SEMOD55424-5 v5The settings available for Generic communication function for Measured Value (MVGAPC) functionallows the user to choose a deadband and a zero deadband for the monitored signal. Values withinthe zero deadband are considered as zero.1MRK 511 358-UUS A Section 18Station communication451Application manual