Table 6:SCILO Logical node dataDO name DO type DA name FC T Signal Mon/CmdDescriptionMod aINC Oper.ctlVal CO - Mod Cmd Mode parameterOper.origin.orCat CO - Mod Cmd Mode parameterOper.origin.orIdent CO - Mod Cmd Mode parameterOper.ctlNum CO - Mod Cmd Mode parameterOper.T CO - Mod Cmd Mode parameterOper.Test CO - Mod Cmd Mode parameterOper.Check CO - Mod Cmd Mode parameterstVal ST - - Mon Mode status parameter for 61850q ST - - Mon Quality: Mode status parameter for61850t ST - - Mon Timestamp: Mode statusparameter for 61850Beh aINS stVal ST - Beh Mon Behaviour parameterq ST - Beh Mon Quality: Behaviour parametert ST - Beh Mon Timestamp: Behaviour parameterEnaCls aSPS stVal ST - EN_CLOSE Mon Close operation at open or interm.or bad pos. is enabledq ST - EN_CLOSE Mon Quality: Close operation at open orinterm. or bad pos. is enabledt ST - EN_CLOSE Mon Timestamp: Close operation atopen or interm. or bad pos. isenabledEnaOpn aSPS stVal ST - EN_OPEN Mon Open operation at closed orinterm. or bad pos. is enabledq ST - EN_OPEN Mon Quality: Open operation at closedor interm. or bad pos. is enabledt ST - EN_OPEN Mon Timestamp: Open operation atclosed or interm. or bad pos. isenabled7.3.3 Switch controller CSWI7.3.3.1 Switch controller SCSWILN type LN prefix LN class Function block nameSCSWI (revision 1) S CSWI SCSWI1MRK 511 349-UEN - Section 7Logical node data model670 series 2.1 IEC 79Communication protocol manual