7424V dcFuse,3A, Type TTerminal Block E12345+-LineNeutralFuse,1A, Type TTerminal Block ELN 85 – 265V50/60Hz171819141516111213789456123Terminal Block C or DDigital OutputCommonLoad910111213141516do1do2do3do4do5do6COMCOMdi1di2di3di4di5di6COMCOMTerminal Blocks C or DInput StateDxx activeSwitch Inputoror5V0VLogic InputLogic StateDxx in-active123456785Vor 0Va01a0217181920+–+–Caution. Use fuse rating – 3A (max.) type T.B - D.C. SupplyFig. 5.9 Mains Power SupplyNote. Relay contacts are fitted with arcsuppression components as standard.Fig. 5.10 Relay ConnectionsInformation.Voltage level 5V. Load: 450Ω min. 15kΩ max.Note. Refer to Fig. 5.5 for terminal numbers.Fig. 5.11 Digital Output ConnectionsFig. 5.12 Digital Input ConnectionsFig. 5.13 Analog Output Connections…5 INSTALLATION5.6 Mains Power Connections – Fig 5.95.7 Relay Output Board Connections – Fig. 5.10Note.• The maximum total combined current flowing through therelays is 36A. The maximum individual relay current is 5A.• The polarity is setup during I/O module configuration –see Section 4.7.2, 3-Relay and 6-Relay Modules.5.8 Hybrid I/O Module Connections5.8.1 Digital Output Connections – Fig 5.11Six digital outputs are provided on the Hybrid option board.5.8.2 Digital Input Connections – Fig 5.12Six digital inputs are provided on Hybrid option boards.5.8.3 Analog Output Connections – Fig 5.13Two analog outputs are provided on the Hybrid option board.Caution. Use fuse rating – 1A (max.) type T.A - A.C. Supply