1MRS755347 SPA-ZC 40099Ethernet AdapterInstallation and Commissioning Manual7.4. SCL conformance statementThe table below defines the support of Substation Configuration Language.Implementations claiming conformance to SCL.2 or SCL.3 may support the ACSIservices defined in the table below.Table 7.4.-1 SCL conformance degreesSCL conformance Client-CR Server-CRBase F/S Value/Range Base F/S SPA-ZC 400/CommentsSCL.1 SCL File for ImplementationAvailable (offline)m m Supported, CIDfile exportSCL.2 SCL File available fromimplementation onlineO o o o Supported, CIDfile can beretrieved onlinewith FTP fromthe deviceSCL.3 SCL implementationreconfiguration supportedonlineO o o o Supportedaa. The CID file is used to configure the device. Notice that you have to preserve the Communication Engineering Tool's (CET) privatesections to configure a device again. CET knows product limitations and it is recommended to use CET only for the configuration.Table 7.4.-2 Supported ACSI services for SCL.2 and SCL.3SCL conformance Client-CR Server-CRBase F/S Value/Range Base F/S SPA-ZC 400/CommentsACSI Services Not SupportedGetFileAttributeValues O o o m Not SupportedGetFile O a o a Not SupportedSetFile O b o b Not SupportedDeleteFile O o o b Not SupportedGetDataValues O c o c Not SupportedSetDataValues O a o a Not SupportedSCL Control Block I i o b Not SupportedSCL File Structure I m i m Not SupportedRemote Creation of SCL File I o i o Not Supporteda. Must be m if support for SCL.2 is declared.b. Must be m if support for SCL.3 is declared.c. Must be m if support for SCL.2 or SCL.3 is declared.