7311.2.1.6. OriginatorTable 11.2.1.6.-1 Step position with transient indicationOriginatorType DefinitionAttribute Name AttributeType Value/ Value Range M/O/C SPA-ZC 402/CommentsorCat ENUMERATED not-supported | bay-control | station-control |remote-control |automatic-bay |automatic-station |automatic-remote |maintenance | processM SupportedorIdent OCTET STRING64 M SupportedTable 11.2.1.6.-2 Values for orCatValue Explanationbay-control Control operation issued from an operator using a clientlocated at bay levelstation-control Control operation issued from an operator using a clientlocated at station levelremote-control Control operation from a remote operater outside thesubstation (e.g. network control center)automatic-bay Control operation issued from an automatic function at baylevelautomatic-station Control operation issued from an automatic function at stationlevelautomatic-remote Control operation issued from an automatic function outside ofthe substationmaintenance Control operation issued from a maintenance / service toolprocess Status change occurred without control action (e.g. externaltrip of a circuit breaker or failure inside the breaker)11.2.1.7. Unit definitionTable 11.2.1.7.-1 UnitUnit Type DefinitionAttribute Name AttributeType Value/ Value Range M/O/C SPA-ZC 402/CommentsSIUnit ENUMERATED According to table inAnnex AM Supportedmultiplier ENUMERATED According to table inAnnex AO SupportedSPA/ Ethernet AdapterSPA to IEC 61850 GatewayInstallation and Commissioning ManualSPA-ZC 402SPA-ZC 4021MRS755380