Specifications42/18-85-EN TZIDC-200, TZIDC-210, TZIDC-220 459.3 TZIDC-2209.3.1 CommunicationSpecification FOUNDATION fieldbus, version 1.5Physical Layer Model 113, 121 (IEC 61158-2)Transmission rate 31.25 Kbit/sBlock types 1 AO Function block1 PID block1 Resource block1 Transducer block1 physical blockBlock class AO block: standardPID block: enhancedResource block: enhancedTransducer block: customNumber of linkage objects 22Device description (DD) Rev. No. 1 (file name 0201.ffo,0201.sym)File Common file format (file name:020101.cff)Max. execution time AO block: 40 millisecondsPID block: 50 millisecondsSupply voltage Power feed from the fieldbus9.0 … c 32.0 V DCMax. permissible voltage 35 V DCPower consumption 11.5 mACurrent in the event of anerror 15 mA (11.5 mA + 3.5 mA)FF Certification Registered with ITK 4.51, Dec.2003IT Camp. Number IT023200Device name ABB TZIDC-200, TZIDC-210,TZIDC-220-TAGDev. ID 0003200028-TZIDC-200, TZIDC-210, TZIDC-220XXXXXXXXXXDevice address Between 10 and 247, defaultaddress 23ATEX certificate for FISCO YesInsensitive to reversedpolarity YesClass LM profile 32L, 31 PSFactory default The positioner is not delivered in analigned state. To adjust theoperating range and controlparameters, an automaticconfiguration must be run on theunit. Otherwise, the transducer blockremains in out-of-service mode.Diagnostic functions Self-diagnostics for the positionerhardware and software, valvediagnostics with enhanced alarmhandling9.3.2 Device nameDevice name ABB TZID-C220XXXXXXXXXXDev. ID 0X3200028-TZID-C220XXXXXXXXXXX9.3.3 OutputRange 0 …6 bar (0 … 90 psi)Air capacityat 1.4 bar (20 psi)supply pressure5.0 kg/h = 3.9 Nm 3 /h=2.3 scfmat 6 bar (90 psi)supply pressure13 kg/h = 10 Nm 3 /h = 6.0 scfmOutput function For single or double-acting actuators,air is vented from actuator or actuatoris blocked in case of (electrical) powerfailureShut-off values End Position 0 % = 0 ... 45 %End position 100 % = 55 … 100 %9.3.4 TravelSteRotation angleUsed range25 … 120° rotary actuators, optionally 270°25 … 60° linear actuatorsTravel timeprolongationSetting range 0 ... 200 seconds, separately for eachdirection9.3.5 Air supplyInstrument air free of oil, water and dust acc. toDIN / ISO 8573-1pollution and oil content according toClass 3 (purity: max. particle size:5 μm, max. particle density:5 mg / m 3 ; oil content: max.concentration: 1 mg / m 3 ; pressuredew point: 10 K below operatingtemperatureSupply pressure 1.4 ... 6 bar (20 ... 90 psi)IMPORTANT (NOTE)Do not exceed the maximum operating pressure of theactuator!Air consumption < 0.1 kg/h / 0.05 scfm (independentof supply pressure)