Ex relevant specifications60 TZIDC, TZIDC-110, TZIDC-120 CI/TZIDC/110/120-EN7.3.2 ATEX Ex nDesignation: II 3 G Ex nA IIC T6 resp. T4 GcDeclaration of conformity: TÜV 02 ATEX 1943 XType: Type of ignition protection "n"Device class: II 3 GStandards: EN 60079-15:2010EN 60079-0:2009II 3 GTemperature classTaAmbient temperature rangeT4 -40 ... 85 °CT6 -40 ... 50 °CElectrical data for II 3 G Ex nA IIC T6 or T4 GcSignal circuit(terminal +11 / -12)U = 9 ... 32 V DCI = 11.5 mAMechanical digital feedback(terminal limit1 +51 / -52 or limit2 +41 / -42)U = 5 ... 11 V DCPlug-in module for shutdown contact input(terminal+51 / -52 or +85 / -86)U = 20 ... 30 V DCSpecial conditions• Devices may only be connected to circuits in zone 2 if they are suitable for operation in zone2 potentially explosive atmospheres and for the conditions prevailing at the installationlocation (manufacturer's declaration or certificate from an inspection authority).• For the "digital feedback with proximity switches" circuit, external measures must beimplemented to prevent the rated voltage from being exceeded by more than 40 % in theevent of transient disturbances.• It is only permissible to connect, disconnect, and switch live circuits during installation ormaintenance, or for the purpose of carrying out repairs. Comment: It is considered veryunlikely that a potentially explosive atmosphere would be present in zone 2 at the same timethat installation or maintenance/repair work was being carried out.• Only non-flammable gases may be used for the pneumatic auxiliary power.• Only use suitable cable entries which meet the requirements of IEC 60079-15.• If the SJ2_S1N (NO) proximity switch is used, the positioner may only be operated at anambient temperature range from -25 ... 85 °C.