Parameter descriptions82 TZIDC, TZIDC-110, TZIDC-120 42/18-84-EN11.2.2 Parameter descriptionwParameter Display Function Parameter Unit Factory setting CustomersettingP1._ STANDARDP1.0 ACTUATOR Actuator type LINEAR, ROTARY --- LINEARP1.1 AUTO_ADJ Auto adjust Function --- --- ---P1.2 TOL_BAND Tolerance band 0,30 … 10,00 % 0,30P1.3 DEADBAND Dead band 0,10 … 10,00 % 0,10P1.4 TEST Test Function --- --- ---P1.5 1) ADRESS Busadresse 1 … 126 --- 126 ---P1.6 EXIT Return to operat. level Function --- --- ---P2._ SETPOINTP2.0 --- --- ---P2.1 --- --- ---P2.2 CHARACT Characteristic curve LINEAR, EP 1:25, 1:50, 25:1, 50:1,USERDEF--- LINEARP2.3 ACTION Action of the output DIRECT, REVERSE --- DIRECTP2.4 SHUT-CLS Shut-off range 0% OFF, 0,1 … 45 % offP2.5 RAMP^ Set point ramp, up OFF, 0,1 … 999,9 sec offP2.6 RAMPˇ Set point ramp, down OFF, 0,1 … 999,9 sec offP2.7 SHUT-OPN Shut-off range 100% OFF, 80.0 … 100 % offP2.8 EXIT Return to operat. level Function --- --- ---P3._ ACTUATORP3.0 MIN_RGE Min. of operating range 0,0 … 100,0 % 0,0P3.1 MAX_RGE Max. of operating range 0,0 … 100,0 % 100,0P3.2 ZERO_POS Zero position CLOCKWISE, CTCLOCKWISE --- CTCLOCKWISEP3.3 EXIT Return to operat. level Function --- --- ---P4._, P.5_ --- --- ---P6._ MAN_ADJP6.0 MIN_VR Min. operating range 0,0 … 100,0 % 0,0P6.1 MAX_VR Max. operating range 0,0 … 100,0 % 100,0P6.2 ACTUATOR Actuator type LINEAR, ROTARY --- LINEARP6.3 SPRNG_Y2 Spring action (Y2) CLOCKWISE, CTCLOCKWISE --- CTCLOCKWISEP6.4 ADJ_MODE Auto adjust mode FULL, STROKE, CTRL_PAR, ZERO_POS, LOCKED--- FULLP6.5 EXIT Return to operat. level Function --- --- ---P7._ CTRL_PARP7.0 KP^ KP value, up 1,0 … 100,0 --- 1,0P7.1 KPv KP value, down 1,0 … 100,0 --- 1,0P7.2 TV ^ TV value, up 0 … 1000 msec 100P7.3 TVv TV value, down 0 … 1000 msec 100P7.4 GOPULSE^ Go pulse, up 0 … 200 msec 0P7.5 GOPULSEv Go pulse, down 0 … 200 msec 0P7.6 Y-OPFSET^ Y offset, up Y-Min … 100,0 % 40,0P7.7 Y-OFFSETv Y offset, down Y-Min … 100,0 % 40,0P7.8 --- --- ---P7.9 TOL_BAND Tolerance band 0,30 … 10,00 % 0,8P7.10 TEST Test Function --- --- ---P7.11 EXIT Return to operat. level Function --- --- ---P8._, P9._,P.10_--- --- ---P11._ FS/IPP11.0 FAIL_POS Save position selection ACTIVE, INACTIV --- INACTIVP11.1 FACT_SET Factory setting Function --- --- ---P11.2 IP_TYP I/P module type NO_F_POS,F_SAFE_1, F_SAFE_2, F_FREEZE1, F_FREEZE2--- NO_F_POSP11.3 EXIT Return to operat. level Function --- --- ---1) only TZIDC-110