Commissioning© 2006 ABB STOTZ-KONTAKT GmbH 44ABB i-bus®EIB / KNX3.4.2 Time switch programFig. 44: “Time switch program” screenMethod of operationThe time switch program sends telegrams with specific group addresses andvalues at the parameterised times. Specific functions are thus triggered inthe ABB i-bus® installation such as switching the lighting in a room on or off.To do so, day routines i.e. switching programs for specific days can bedefined. A week routine with the assignment of day routines to weekdayscan also be set.In the time switch program, you can- define 15 day routines i.e. 15 different time switch programs for the periodbetween 00:00 and 23:59,- assign a total of 800 switching times,- define the week routine i.e. assign a day routine to each day of the week,- define daylight saving times for 10 years in advance,- assign 100 individual periods – so-called special days – which deviatefrom the normal week routine and- display an overview of the time switch program.