ABB i-bus£ KNX Commissioning© 2009 Busch-Jaeger Elektro GmbH – A Company of the ABB Group 173.2.2 "TemperatureMeasurement" parameterwindowOffset for room temp. meas.(measured value changed by (-128..127)x0.1 K)Options: - -128- …- 0- …- 127Value range –128..127 corresponds to –12.8K..12.7KIf the actual temperature is recorded internally, it may be falsified by anadditional internal heat source, e.g. bus or network coupler. The falsifiedvalue can be adjusted with the setting "calibration value for ambienttemperature measurement".Setpoint larger when sending changeOptions: - Inactive- 0.1 K- 0.2 K- 0.3 K- 0.4 K- 0.5 K- 0.6 K- 0.7 K- 0.8 K- 0.9 K- 1.0 KIf this parameter is set to a difference, the associated 2-byte communicationobject "Current temperature" sends its current temperature whenever thisparameter changes.